Description
| Parameter |
|---|
| Heat-shrinkable stress control sleeves |
| Non-tracking, heat-shrinkable outer insulation |
| Water and corrosion-resistant |
| Different creepage distances available |
| Suitable for compression and mechanical lugs |
| Suitable for wide range of connectors |
| No oil or compound filling |
| Tested under International standards |
Technical Information
| Sr. No. | Particulars | Specifications |
|---|---|---|
| 1 | Applicable Standards | IEC 60840 |
| 2 | Nominal System Voltage | 66kV Phase to Phase |
| 3 | Highest System Voltage | 72.5kV |
| 4 | Impulse Voltage at 95 to 1000C temperature | 325kV (Peak) |
| 5 | Frequency | 50 Hz. |
| 6 | AC High Voltage withstand test 15 min dry | 95 kV |
| 7 | Partial Discharge Test at Ambient
Pre-Stressed at 1.75U0 (67kV) 10sec Measured at 1.5U0 (57kV) |
Less than 5pC |
| 8 | Partial Discharge Test at Elevated (95-1000C)
Pre-Stressed at 1.75U0 (67kV) 10sec Measured at 1.5U0 (57kV) |
Less than 5pC |
| 9 | Heating Cycle Voltage Test | |
|
24hr | |
|
8hr | |
|
16hr | |
|
95 to 1000C | |
|
76kV | |
|
20 | |
| 10 | Short Circuit Current | Same as Cable size subject to max. Conductor temperature of 250oC. |
| 11 | Creepage (outdoor) | 2300mm min. |
| 12 | Accessories | Mechanical connectors (if ordered separately for terminations) |
| 13 | Method of Stress Control | Heat Shrinkable type |
| 14 | Tubing’s & Molded parts | Heat Shrinkable type |
| 15 | Non-Tracking material | Confirming as per ASTM D-2303 |
| 16 | Di-electric strength of insulating material | 10 kV/mm min |
| Heat Shrink type Indoor/Outdoor Termination and Straight Through Joint for 66kV (E) | ||